  • Maximum switching current of 5 A/30 V DC (type DIN rail), 1 A/30 V DC (type in-built), 0.5 A/42.4 V AC (both variants)
  • Low current consumption
  • Maintains LSN loop functions in the event of wire interruption or short-circuit thanks to two integrated isolators

BOSCH - FLM-420-RLV1 ALÇAK GERİLİMLİ RÖLE ARAYÜZÜ MODÜLÜ

Stok kodu: FLM-420-RLV1
  • LSN ;
    LSN input voltage
    : 15 V DC to 33 V DC (min. to max.)
    Max. current consumption from LSN: 1.75 mA
    Relay (low voltage): Normally closed, common and normally open contact (NC/COM/NO)
    Contact load (ohm resistive load): FLM‑420‑RLV1‑E    
    Max. switching current and voltage: 1 A / 30 V DC 0.5 A / 42.4 V AC
    Min. switching current and voltage: 0.01 mA / 10 mV DC 0.01 mA / 10 mV AC
    Max. frequency AC: 100 Hz
    Contact load (ohm resistive load): FLM‑420‑RLV1‑D    
    Max. switching current and voltage: 5 A / 30 V DC 0.5 A / 42.4 V AC
    Min. switching current and voltage: 0.1 mA / 100 mV DC 0.1 mA / 100 mV AC
    Max. AC frequency: 100 Hz
    Minimum activation time of the connected device: > 20 ms
    Connections ;
    FLM-420-RLV1-E
    : 12 screw terminals
    FLM-420-RLV1-D: 6 threaded terminals
    Permitted wire cross-section ;
    FLM-420-RLV1-E
    : 0.6 to 2.0 mm2
    FLM-420-RLV1-D: 0.6 to 3.3 mm2
    Address setting ;
    FLM-420-RLV1-E
    : 8 DIP switches
    FLM-420- RLV1-D: 3 rotary switches
    Housing material ;
    FLM-420- RLV1-E
    : ABS/PC blend
    FLM-420- RLV1-D with adapter: PPO (Noryl)
    Color ;
    FLM-420- RLV1-E
    : Signal white, RAL 9003
    FLM-420- RLV1-D: Off-white, similar to RAL 9002
    Dimensions ;
    FLM-420- RLV1-E: Approx. 50 mm x 22 mm (Ø x H)
    FLM-420- RLV1-D with adapter: Approx. 110 x 110 x 48 mm (W x H x D)
    Weight: Without / with packaging
    FLM-420- RLV1-E: Approx. 35 g / 130 g
    FLM-420- RLV1-D: Approx. 150 g / 235 g
    Permitted operating temperature: -20 °C to +55 °C
    Permitted storage temperature: -25 °C to +80 °C
    Permitted rel. humidity: < 96% (non-condensing)
    Classes of equipment as per IEC 60950: Class III equipment
    Protection class as per IEC 60529: IP 30